C h a p t e r 5 P a r a m e t e r s a n d F u n c t i o n s
5 - 11
_5
6F
40112
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
70
40113
Dropout setpoint (total
apparent power value
below this value
clears alarm)
0.000 – 99999.999
float
kVA
4
R/W
71
40114
72
40115
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Lead PF
73
40116
Alarm enable
0: Disable
1: Enable
word
2
R/W
74
40117
Pickup setpoint (total
power factor value
below this value
triggers alarm)
0.00000 – 1.00000
float
4
R/W
75
40118
76
40119
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
77
40120
Dropout setpoint
(total power factor
value exceeding this
value clears alarm)
0.00000 – 1.00000
float
4
R/W
78
40121
79
40122
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Lag PF
7A
40123
Alarm enable
0: Disable
1: Enable
word
2
R/W
7B
40124
Pickup setpoint (total
power factor value
below this value
triggers alarm)
0.00000 – 1.00000
float
4
R/W
7C
40125
Summary of Contents for DPM-C530
Page 2: ......
Page 3: ......
Page 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Page 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Page 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...