C h a p t e r 5 P a r a m e t e r s a n d F u n c t i o n s
5 - 1 5
_5
Alarm – Over Apparent Power Demand
A4
40165
Alarm enable
0: Disable
1: Enable
word
2
R/W
A5
40166
Pickup setpoint
(apparent power
demand value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
kW
4
R/W
A6
40167
A7
40168
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
A8
40169
Dropout setpoint
(apparent power
demand value below
this value clears
alarm)
0.000 – 99999.999
float
kW
4
R/W
A9
40170
AA
40171
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Frequency
AB
40172
Alarm enable
0: Disable
1: Enable
word
2
R/W
AC
40173
Pickup setpoint
(frequency value
exceeding this value
triggers alarm)
0.0000 – 99.9999
float
Hz
4
R/W
AD
40174
AE
40175
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
AF
40176
Dropout setpoint
0.0000 – 99.9999
float
Hz
4
Summary of Contents for DPM-C530