D P M – C 5 3 0 O p e r a t i o n M a n u a l
5 - 1 4
_5
97
40152
Pickup setpoint
(active power demand
value exceeding this
value triggers alarm)
0.000 – 99999.999
float
kW
4
R/W
98
40153
99
40154
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
9A
40155
Dropout setpoint
(active power demand
value below this value
clears alarm)
0.000 – 99999.999
float
kW
4
R/W
9B
40156
9C
40157
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Reactive Power Demand
9D
40158
Alarm enable
0: Disable
1: Enable
word
2
R/W
9E
40159
Pickup setpoint
(reactive power
demand value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
kW
4
R/W
9F
40160
A0
40161
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
A1
40162
Dropout setpoint
(reactive power
demand value below
this value clears
alarm)
0.000 – 99999.999
float
kW
4
R/W
A2
40163
A3
40164
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W