D P M – C 5 3 0 O p e r a t i o n M a n u a l
5 - 1 6
_5
B0
40177
(frequency value
below this value
clears alarm)
R/W
B1
40178
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Under Frequency
B2
40179
Alarm enable
0: Disable
1: Enable
word
2
R/W
B3
40180
Pickup setpoint
(frequency value
below this value
triggers alarm)
0.0000 – 99.9999
float
Hz
4
R/W
B4
40181
B5
40182
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
B6
40183
Dropout setpoint
(frequency value
exceeding this value,
alarm cleared)
0.0000 – 99.9999
float
Hz
4
R/W
B7
40184
B8
40185
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over THD Voltage
B9
40186
Alarm enable
0: Disable
1: Enable
word
2
R/W
BA
40187
Pickup setpoint (THD
voltage value
exceeding this value
triggers alarm)
0.000 – 999.999
float
%
4
R/W
BB
40188
BC
40189
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W