D P M - C 5 3 0 O p e r a t i o n M a n u a l
2 - 2
_2
2.1
Electrical Characteristics
Input
Voltage Connection
1PH2W, 1 CT
3PH3W,
Δ
connection, 3 CT, 2 PT
1PH3W, 2 CT
3PH4W, Y connection, 3 CT, No PT
3PH3W,
Δ
connection, 3 CT, No PT
3PH4W, Y connection, 3 CT, 3 PT
3PH3W,
Δ
connection, 2 CT, No PT
3PH4W, Y connection, 2 CT, 3 PT
Rated Voltage
Line voltage: 35–690 VAC (L-L)
Phase voltage: 20–400 VAC (L-N)
Rated Current
1 A / 5 A
Frequency
50/60 Hz
Harmonic Distortion
for Individual
Current/Voltage
21
Voltage Input
Measuring Category: CAT III
Alarm
Set up multi-level alarms
10 multi-level alarms
Power
Operating range
80–265 VAC (maximum power: 4.6 W
)
100–300 VDC
Frequency
Operating frequency
50/60 Hz
Communication
RS-485 port
Modbus-RTU, Modbus ASCII, BACnet
MS/TP
Baud rate 9600 / 19200 / 38400 bps
Measurement Accuracy
Electric quantities
Voltage, current
± 0.5%
Electric
energy
Real power
± 0.5%
Real power, reactive
power, apparent power
± 0.5%
Reactive
power
± 0.5%
Power factor
± 0.5%
Total Harmonic
Distortion for Current
± 1%
Real power
± 0.5%
Total Harmonic
Distortion for Voltage
± 1%
Reactive power
± 0.5%
Frequency
± 0.5%
Apparent power
± 0.5%
Harmonic
± 1%
Summary of Contents for DPM-C530
Page 2: ......
Page 3: ......
Page 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Page 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Page 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...