Chapter 4 Parameters
|
Revision Dec. 2008, 04VE, SW V2.05
4-27
Group 3 Analog Input/Output Parameters
In version 2.02, the parameters are from Pr.03-00 to Pr.03-20. The settings for Pr.03-00 to
Pr.03-02 are from 0 to 10
Pr.
Explanation
Settings
Factory
Setting
VF VFPG SVC FOCPG TQCPG
03-00
Analog Input 1 (AVI)
2: torque command (torque limit under
speed mode)
0
○
3: Torque compensation command
○
○
○
○
○
03-01
Analog Input 2 (ACI)
4: PID target value (refer to group 8)
○
○
○
○
5: PID feedback signal (refer to group
8)
○
○
○
○
03-02
Analog Input 3 (AUI)
6: P.T.C. thermistor input value
○
○
○
○
○
7: Positive torque limit
○
8: Negative torque limit
○
9: Regenerative torque limit
○
10: Positive/negative torque limit
○
03-20
Analog Output Value in REV Direction
0: Absolute value in REV direction
1: Output 0V in REV direction
2: Enable output voltage in REV
direction
0
○
○
○
○
○
Group 6 Protection Parameters
In version 2.02, the parameters are from Pr.06-00 to Pr.06-31. The settings of Pr.06-01 are
shown as follows. The settings for Pr.06-17 to Pr.06-22 are from 0 to 62.
Pr.
Explanation
Settings
Factory
Setting
VF VFPG SVC FOCPG TQCPG
0.0: Disable
350.0~450.0Vdc 380.0
○
○
○
○
○
06-01
Over-voltage Stall Prevention
700.0~900.0Vdc 760.0
○
○
○
○
○
06-17
Present Fault Record
0
○
○
○
○
○
06-18
Second Most Recent Fault Record
0
○
○
○
○
○
06-19
Third Most Recent Fault Record
0
○
○
○
○
○
06-20
Fourth Most Recent Fault Record
0
○
○
○
○
○
06-21
Fifth Most Recent Fault Record
0
○
○
○
○
○
06-22
Sixth Most Recent Fault Record
0
○
○
○
○
○
0: No fault
1: Over-current during acceleration
(ocA)
2: Over-current during deceleration
(ocd)
3: Over-current during constant speed
(ocn)
4: Ground fault (GFF)
5: IGBT short-circuit (occ)
6: Over-curent at stop (ocS)
7: Over-voltage during acceleration
(ovA)
8: Over-voltage during deceleration
(ovd)
9: Over-voltage during constant speed
(ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration
(LvA)
12: Low-voltage during deceleration
(Lvd)
13: Low-voltage during constant speed
(Lvn)
14: Low-voltage at stop (LvS)
15: Phase loss (PHL)
16: IGBT heat sink over-heat (oH1)
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Summary of Contents for VFD-VE
Page 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...