Chapter 4 Parameters
|
4-136
Revision Dec. 2008, 04VE, SW V2.05
08-03
Derivative Control (D)
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 0.00
Settings
0.00 to 1.00 sec
This parameter determines the damping effect for the PID feedback loop. If the differential time
is long, any oscillation will quickly subside. If the differential time is short, the oscillation will
subside slowly.
08-04
Upper limit for Integral Control
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 100.0
Settings
0.0
to
100.0%
This parameter defines an upper bound or limit for the integral gain (I) and therefore limits the
Master Frequency.
The formula is: Integral upper bound = Maximum Output Frequency (Pr.01-00) x (Pr.08-04).
08-05
PID Output Frequency Limit
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 100.0
Settings
0.0
to
110.0%
This parameter defines the percentage of output frequency limit during the PID control. The
formula is Output Frequency Limit = Maximum Output Frequency (Pr.01-00) X Pr.08-05 %.
This parameter will limit the Maximum Output Frequency.
08-06
PID Offset
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 0.0
Settings
-100.0 to 100.0%
08-07
PID Delay Time
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 0.0
Settings
0.0 to 2.5 sec
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Summary of Contents for VFD-VE
Page 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...