Chapter 4 Parameters
|
Revision Dec. 2008, 04VE, SW V2.05
4-99
03-19
Gain for Analog Output 1
Unit: 0.1
03-22
Gain for Analog Output 2 (need to be used with EMV-
APP01)
Unit: 0.1
03-25
Gain for Analog Output 3 (need to be used with EMV-
APP01)
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG TQCPG
Factory setting: 100.0
Settings
0 to 200.0%
It is used to adjust the analog voltage level that terminal AFM outputs.
This parameter is set the corresponding voltage of the analog output 0.
03-20
Analog Output 1 Value in REV Direction
03-23
Analog Output 2 Value in REV Direction
03-26
Analog Output 3 Value in REV Direction
Control
mode
VF VFPG SVC
FOCPG TQCPG
Factory setting: 0
Settings
0
Absolute value in REV direction
1
Output 0V in REV direction
2
Enable output voltage in REV direction
03-18
03-21
03-24
03-20=0
03-23=0
03-26=0
03-20=1
03-23=1
03-26=1
10V( 20mA)
03-20=2
03-23=2
03-26=2
5V
( 12mA)
10V( 20mA)
0V
( 0mA)
10V( 20mA)
0V
( 0mA)
F requenc y
F requenc y
Selections for the analog output dir ec ti on
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Summary of Contents for VFD-VE
Page 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...