Chapter 4 Parameters
|
Revision Dec. 2008, 04VE, SW V2.05
4-63
01-08
4th Output Voltage Setting 1
Unit: 0.1
Control
mode
VF
VFPG
Settings
230V series
0.1 to 255.0V
Factory Setting: 0.0
460V series
0.1 to 510.0V
Factory Setting: 0.0
01-41
4th Output Frequency Setting 2
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG TQCPG
Factory Setting: 0.00
Settings 0.00~600.00Hz
01-42
4th Output Voltage Setting 2
Unit: 0.1
Control
mode
VF
VFPG
Settings
230V series
0.1 to 255.0V
Factory Setting: 0.0
460V series
0.1 to 510.0V
Factory Setting: 0.0
V/f curve setting is usually set by the motor’s allowable loading characteristics. Pay special
attention to the motor’s heat dissipation, dynamic balance, and bearing lubricity, if the loading
characteristics exceed the loading limit of the motor.
For the V/f curve setting, it should be Pr.01-01
≥
Pr.01-03
≥
Pr.01-05
≥
Pr.01-07. There is no
limit for the voltage setting, but a high voltage at the low frequency may cause motor damage,
overheat, stall prevention or over-current protection. Therefore, please use the low voltage at
the low frequency to prevent motor damage.
Pr.01-35 to Pr.01-42 is the V/f curve for the motor 2. When multi-function input terminals Pr.02-
01 to Pr.02-14 is set to 14 and enabled or switch to the
Δ
-connection, the AC motor drive will
act as the 2nd V/f curve.
The V/f curve for the motor 1 is shown as follows. The V/f curve for the motor 2 can be
deduced from it.
01-05 01-03
01-01
01-06
01-04
01-02
01-00
01-07
01-08
01-09
01-11
01-10
1st Ou tput
Voltage Setting
Output Freque ncy
Low er Limit
Frequ ency outpu t
ranges limitat ion
Reg ular V/f Curve
Special V/f Cu rve
Voltage
4th Freq.
Start Freq.
3rd Freq.
2nd Freq.
1st Freq.
Maximum Outp ut
Frequ ency
V/f Curve
2nd Ou tput
Voltage Setting
3 rd Ou tput
Voltage Setting
4th Ou tput
Voltage Setting
Output Freque ncy
Upp er Limit
Frequ ency
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Summary of Contents for VFD-VE
Page 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...