Chapter 4 Parameters
|
4-92
Revision Dec. 2008, 04VE, SW V2.05
If this parameter is used without DC brake, it will be invalid. Refer to the following operation
timing.
Multi-function output
(mec hanic al brak e
release)
Pr.02- 11 to 02- 14= 12
RUN
STOP
A
B=A
zero
speed
zero
speed
Time
frequency
command
output
frequency
RUN/ST OP
mechanical brake
brake
brake
release
02-32
Output Current Level Setting for External Terminals
Unit:1
Control
mode
VF VFPG SVC
FOCPG TQCPG
Factory setting: 0
Settings
0~100%
When output current is higher or equal to Pr.02-32, it will activate multi-function output terminal
(Pr.02-11 to Pr.02-14 is set to 27).
When output current is lower than Pr.02-32, it will activate multi-function output terminal
(Pr.02-11 to Pr.02-14 is set to 28).
02-33
Output Boundary for External Terminals
Unit:0.01
Control
mode
VF VFPG SVC
FOCPG TQCPG
Factory setting: 0.00
Settings
0.00~+-60.00Hz
When output frequency is higher than Pr.02-33, it will activate the multi-function terminal
(Pr.02-11 to Pr.02-14 is set to 29).
When output frequency is lower than Pr.02-33, it will activate the multi-function terminal
(Pr.02-11 to Pr.02-14 is set to 30).
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Summary of Contents for VFD-VE
Page 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...