Chapter 4 Parameters
|
4-144
Revision Dec. 2008, 04VE, SW V2.05
08-26
PID Target Value of Tension/Line Speed
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 50.0
Settings 0.0
to
100.0%
The setting range 0.0 to 100.0% corresponds to tension feedback 0~10V/0~max. line speed
(Pr.08-38).
Example:
In tension mode, when Pr.08-21 is set to 1 (Tension closed-loop, speed mode), the setting 14
of Pr.03-00~03-02 (PID target value of tension) corresponds to tension feedback 0~10V.
In tension mode, when Pr.08-21 is set to 2 (Line speed closed-loop, speed mode), the setting
12 of Pr.03-00~03-02 (line speed) corresponds to 0~max. line speed (Pr. 08-38).
08-27
Source of Tension/Line Speed PID Feedback
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 0
Settings
0
Analog input (Pr. 03-00~03-02 is set to 11 PID feedback of tension)
1
Pulse
input
(Pr.08-40)
08-28
Auto-tuning Tension PID
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 0
Settings
0
Disable
1
Reel diameter (08-29~08-30 corresponds to 08-44, 08-32~08-33
corresponds to 08-43)
2
Frequency (08-29~08-30 corresponds to 01-07, 08-32~08-33
corresponds to 01-00)
When Pr.08-28 is set to 1:
08-29
08-30
P.I.D
0
08-32
08-33
08-44
08-43
Dmax
Dmin
reel
diameter
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Summary of Contents for VFD-VE
Page 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...