Chapter 4 Parameters
|
Revision Dec. 2008, 04VE, SW V2.05
4-173
10-02
Encoder Feedback Fault Treatment
Control
mode
VFPG
FOCPG
TQCPG
Factory Setting: 2
Settings
0
Warn and keep operating
1
Warn and RAMP to stop
2
Warn and COAST to stop
10-03
Detection Time for Encoder Feedback Fault
Unit: 0.01
Control
mode
VFPG
FOCPG
TQCPG
Factory Setting: 1.00
Settings
0.00 to 10.00 sec
When encoder loss, encoder signal error, pulse signal setting error or signal error, if time
exceeds the detection time for encoder feedback fault (Pr.10-03), the encoder signal error will
occur. Refer to the Pr.10-02 for encoder feedback fault treatment.
10-04
ASR (Auto Speed Regulation) control (P) 1
Unit: 0.1
Control
mode
VFPG
FOCPG
TQCPG
Factory Setting: 10
Settings
0 to 40 Hz
10-05
ASR (Auto Speed Regulation) control (I) 1
Unit: 0.001
Control
mode
VFPG
FOCPG
TQCPG
Factory Setting: 0.100
Settings
0.000 to 10.000 sec
10-06
ASR (Auto Speed Regulation) control (P) 2
Unit: 0.1
Control
mode
VFPG
FOCPG
TQCPG
Factory Setting: 10
Settings
0 to 40Hz
10-07
ASR (Auto Speed Regulation) control (I) 2
Unit: 0.001
Control
mode
VFPG
FOCPG
TQCPG
Factory Setting: 0.100
Settings
0.000 to 10.000 sec
10-21
P Gain of Zero Speed
Unit: 1
Control
mode
VFPG
FOCPG
TQCPG
Factory Setting: 10
Settings
0 to 40Hz
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Summary of Contents for VFD-VE
Page 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...