Chapter 4 Parameters
|
Revision Dec. 2008, 04VE, SW V2.05
4-15
Pr.
Explanation
Settings
Factory
Setting
VF VFPG SVC FOCPG TQCPG
2) 2:
Disable
06-28
Electronic Thermal
Characteristic for
Motor 2
30.0~600.0 sec
60.0
○
○
○
○
○
06-29
PTC (Positive
Temperature
Coefficient) Detection
Selection
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
0
○
○
○
○
○
06-30
PTC Level
0.0~100.0%
50.0
○
○
○
○
○
06-31
Filter Time for PTC
Detection
0.00~10.00sec 0.20
○
○
○
○
○
06-32
Output Frequency for
Malfunction
0.00~655.35 Hz
Read-
only
○
○
○
○
○
06-33
Output Voltage for
Malfunction
0.0~6553.5 V
Read-
only
○
○
○
○
○
06-34
DC Voltage for
Malfunction
0.0~6553.5 V
Read-
only
○
○
○
○
○
06-35
Output Current for
Malfunction
0.00~655.35 Amp
Read-
only
○
○
○
○
○
06-36
IGBT Temperature for
Malfunction
0.0~6553.5 °C
Read-
only
○
○
○
○
○