Chapter 4 Parameters
|
Revision Dec. 2008, 04VE, SW V2.05
4-183
11-07
Detection Time for Phase-loss
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG TQCPG
Factory Setting: 0.20
Settings
0.01 to 600.00 sec
11-09
Level of Phase-loss
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG TQCPG
Factory Setting: 60.0
Settings 0.0
to
320.0
11-29
Accumulative Operation Time of Phase-loss
Unit: 1
Control
mode
VF VFPG SVC
FOCPG TQCPG
Factory Setting: 0
Settings
0 to 65535 (hour)
When the power phase-loss occurs and it exceeds the level (Pr.11-09) and the detection
time(Pr.11-07), it will execute the phase-loss protection(Pr.06-02). The AC motor drive will
record the operation time during phase-loss in Pr.11-29.
If it is set to 0 or a larger number, it will short the life of rectifier and capacitors in the AC motor
drive.
11-08
Reserved
11-10
Speed Feed Forward Gain
Unit: 1
Control
mode
FOCPG
Factory Setting: 0
Settings
0 to 100%
It is used to improve the speed response.
ASR
10-09
00-20
+
+
+
07-32~07-35
-
11-10
+
Tq Bias
Speed feed
forward gain
speed feedback
Torque limit
Torque
command
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Summary of Contents for VFD-VE
Page 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Page 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...