Chapter 4 Parameters
|
Revision May 2008, ME14, SW V3.04
4-33
Pr.39
Multi-function Input Terminal (M2)
Factory Setting: 05
Pr.40
Multi-function Input Terminal (M3)
Factory Setting: 06
Pr.41
Multi-function Input Terminal (M4)
Factory Setting: 07
Pr.42
Multi-function Input Terminal (M5)
Factory Setting: 08
Settings 00 to 32
Settings
Function
Description
00
No Function
01
Output OFF (N.O.)
(enabled when running)
02
Output OFF (N.C.)
(enabled when running)
When it is set to 01 or 02, AC drive output will stop
immediately. If there is start signal after stopping, the output
will start from the minimum frequency.
03
External Fault (N.O.)
04
External Fault (N.C.)
Parameter values 3 and 4 program Multi-Function Input
Terminals: M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or
M5 (Pr.42) to be External Fault (E.F.) inputs.
GND
E.F.(N.O.)
setting by 3
E.F(N.C.)
setting by 4
Mx "Close": Operation available.
Mx "Open":Operation available.
Note: When an External Fault input signal is received, the AC
drive output will turn off, drive will display
“
E.F.
”
on
Digital Keypad, and the motor will coast. Normal
operation can resume after the External Fault is cleared
and the AC drive is reset.
Summary of Contents for VFD-M Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 12: ...Chapter 1 Introduction Revision May 2008 ME14 SW V3 04 1 3 1 1 4 External Parts and Labels ...
Page 17: ...Chapter 1 Introduction 1 8 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 21: ...Chapter 2 Installation and Wiring 2 4 Revision May 2008 ME14 SW V3 04 Good Not allowed ...
Page 121: ...Chapter 4 Parameters 4 86 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 149: ...Appendix B Accessories B 4 Revision May 2008 ME14 SW V3 04 ...