B.2 Non-fuse Circuit Breaker Chart
The fuse should comply with UL248 and the breaker should comply with UL489.
(Note: Please select enough current capacity of NFB.)
1-phase 3-phase
Model Name
Recommended
non-fuse breaker
(A)
Model Name
Recommended
non-fuse breaker
(A)
VFD002M11A 15 VFD004M23A 5
VFD004M11A 20 VFD007M23A 10
VFD007M11A 30 VFD015M23A 20
VFD004M21A 15 VFD007M43B 5
VFD007M21A 20 VFD007M53A 5
VFD015M21A 30 VFD015M43B 10
VFD004M21B 15 VFD015M53A 5
VFD007M21B 20 VFD022M23B 30
VFD015M21B 30 VFD022M43B 15
VFD022M21A 50 VFD022M53A 10
VFD037M23A
40
VFD037M43A
20
VFD037M53A
20
VFD055M23A
50
VFD055M43A
30
VFD055M53A
20
VFD075M43A
40
VFD075M53A
30