Chapter 4 Parameters
|
Revision May 2008, ME14, SW V3.04
4-35
Settings
Function
Description
09 Jog
Operation
Parameter value 09 programs Multi-Function Input Terminal:
M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)
for Jog control.
GND
Mx "Close": Operation available
9 jog operation
command
Note: Jog operation programmed by 9 can only be initiated
while the motor is stop. (Refer to Pr.15, Pr.16.)
10
Accel/Decel Speed
Inhibit
Parameter value 10 programs Multi-Function Input Terminal:
M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)
for Accel/Decel Inhibit. After receiving this command, the AC
Drive stops accelerating or decelerating and maintains a
constant speed.
Frequency
Master Frequency
Accel inhibit
Accel inhibit
Actual operation frequency
Decel
inhibit
Decel
inhibit
Time
Mx-GND
Operation
command
ON
ON
ON
ON
ON
OFF