Appendix B Accessories
|
B-10
Revision May 2008, ME14, SW V3.04
B.5 Zero Phase Reactor (RF220X00A)
Dimensions are in millimeter.
Recommended Wire
Size
Cable
type
(
Note
) AWG mm
2
Nominal
(mm
2
)
Qty.
Wiring
Method
≦
10
≦
5.3
≦
5.5
1
Diagram
A
Single-
core
≦
2
≦
33.6
≦
38
4
Diagram
B
≦
12
≦
3.3
≦
3.5
1
Diagram
A
Three-
core
≦
1
≦
42.4
≦
50
4
Diagram
B
Note:
600V Insulated Unshielded Cable.
Power
Supply
Zero Phase Reactor
MOTOR
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Power
Supply
Zero Phase Reactor
MOTOR
Note 1:
The table above gives
approximate wire size for the zero phase
reactors but the selection is ultimately
governed by the type and diameter of
cable fitted i.e. the cable must fit through
the center hole of zero phase reactors.
Note 2:
Only the phase conductors should
pass through, not the earth core or screen.
Note 3:
When long motor output cables
are used, an output zero phase reactor
may be required to reduce radiated
emissions from the cable.
Diagram B
Please put all wires through
4 cores
in
series without winding.
Diagram A
Please wind each wire
4 times
around the
core. The reactor must be put at inverter side
as close as possible.
Summary of Contents for VFD-M Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 12: ...Chapter 1 Introduction Revision May 2008 ME14 SW V3 04 1 3 1 1 4 External Parts and Labels ...
Page 17: ...Chapter 1 Introduction 1 8 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 21: ...Chapter 2 Installation and Wiring 2 4 Revision May 2008 ME14 SW V3 04 Good Not allowed ...
Page 121: ...Chapter 4 Parameters 4 86 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 149: ...Appendix B Accessories B 4 Revision May 2008 ME14 SW V3 04 ...