Chapter 4 Parameters
|
Revision May 2008, ME14, SW V3.04
4-13
Parameter
Explanation
Settings
Factory
Setting
Customer
Pr.145
Total operation time
(Minutes)
Read Only
Pr.146 Line
start
Lockout
00: Disable
01: Enable
00
Pr.147
Decimal Number of
Accel / Decel Time
00: One decimal
01: Two decimals
00
Pr.148
Number of Motor
Poles
02 to 20
04
Pr.149
Gear Ratio for Simple
Index Function
4 to 1000
200
Pr.150
Index Angle for Simple
Index Function
00.0 to 360.0
180.0
Pr.151
Deceleration Time for
Simple Index Function
0.00 to 100.00 sec
0.00
Pr.152
Skip Frequency Width 0.00 to 400.0Hz
0.00
Pr.153
Bias Frequency Width 0.00 to 400.0Hz
0.00
Pr.154 Reserved
Pr.155
Compensation
Coefficient for Motor
Instability
0.0: Disable
0.1 to 5.0 (recommended setting d2.0)
0.0
Pr.156
Communication
Response Delay Time
0 to 200 (x500us)
0
Pr.157
Communication Mode
Selection
0: Delta ASCII
1: Modbus
1