Appendix B Accessories
|
Revision May 2008, ME14, SW V3.04
B-15
Choose suitable motor cable and precautions
Improper installation and choice of motor cable will affect the performance of EMI filter. Be sure to
observe the following precautions when selecting motor cable.
1.
Use the cable with shielding (double shielding is the best).
2.
The shielding on both ends of the motor cable should be grounded with the minimum length
and maximum contact area.
3.
Remove any paint on metal saddle for good ground contact with the plate and shielding.
Remove any paint on metal saddle for good ground contact with
the plate and shielding.
saddle
the plate with grounding
Saddle on both ends
Saddle on one end