Chapter 4 Parameters
|
Revision May 2008, ME14, SW V3.04
4-9
Parameter
Explanation
Settings
Factory
Setting
Customer
Pr.78
PLC Operation Mode
00: Disable PLC operation
01: Execute one program cycle
02: Continuously execute program cycles
03: Execute one program cycle step by step
04: Continuously execute one program cycle
step by step
00
Pr.79
PLC FWD/REV
Motion
00 to 127
00
Pr.80
Identity Code of the
AC Motor Drive
Read only
##
Pr.81
Time Duration of 1st
Step Speed
00 to 9999 sec
00
Pr.82
Time Duration of 2nd
Step Speed
00 to 9999 sec
00
Pr.83
Time Duration of 3rd
Step Speed
00 to 9999 sec
00
Pr.84
Time Duration of 4th
Step Speed
00 to 9999 sec
00
Pr.85
Time Duration of 5th
Step Speed
00 to 9999 sec
00
Pr.86
Time Duration of 6th
Step Speed
00 to 9999 sec
00
Pr.87
Time Duration of 7th
Step Speed
00 to 9999 sec
00
Pr.88
Communication
Address
01 to 254
01
Pr.89 Transmission
Speed
00: 4800 bps
01: 9600 bps
02: 19200 bps
03: 38400 bps
01
Pr.90
Transmission Fault
Treatment
00: Warn and Continue Operating
01: Warn and RAMP to Stop
02: Warn and COAST to Stop
03: Keep Operation without Warning
03
Pr.91
Time Out Detection
0.0: Disable
0.1 to 120.0 sec
0.0
Pr.92
Communication
Protocol
00: MODBUS ASCII mode, <7,N,2>
01: MODBUS ASCII mode, <7,E,1>
02: MODBUS ASCII mode, <7,O,1>
03: MODBUS RTU mode, <8,N,2>
04: MODBUS RTU mode, <8,E,1>
05: MODBUS RTU mode, <8,O,1>
00
Summary of Contents for VFD-M Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 12: ...Chapter 1 Introduction Revision May 2008 ME14 SW V3 04 1 3 1 1 4 External Parts and Labels ...
Page 17: ...Chapter 1 Introduction 1 8 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 21: ...Chapter 2 Installation and Wiring 2 4 Revision May 2008 ME14 SW V3 04 Good Not allowed ...
Page 121: ...Chapter 4 Parameters 4 86 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 149: ...Appendix B Accessories B 4 Revision May 2008 ME14 SW V3 04 ...