Chapter 4 Parameters
|
4-10
Revision May 2008, ME14, SW V3.04
Parameter
Explanation
Settings
Factory
Setting
Customer
Pr.93
Accel 1 to Accel 2
Frequency Transition
0.01 to 400.0
0.00: Disable
0.00
Pr.94
Decel 1 to Decel 2
Frequency Transition
0.01 to 400.0
0.00: Disable
0.00
Pr.95
Auto Energy Saving
00: Disable auto energy saving
01: Enable auto energy saving
00
Pr.96
Counter Countdown
Complete
00 to 9999
00
Pr.97
Preset counter
countdown
00 to 9999
00
Pr.98
Total Time Count from
Power On (Days)
00 to 65535 days
Read
Only
Pr.99
Total Time Count from
Power On (Minutes)
00 to 1440 minutes
Read
Only
Pr.100 Software
Version
##
Pr.101
Auto Adjustable
Accel/Decel
00: Linear Accel/Decel
01: Auto Accel, Linear Decel
02: Linear Accel, Auto Decel
03: Auto Accel/Decel
04: Linear Accel/Decel Stall Prevention
during Deceleration
00
Pr.102
Auto Voltage
Regulation (AVR)
00: AVR function enabled
01: AVR function disabled
02: AVR function disabled when stops
03: AVR function disabled when decel
00
Pr.103
Auto tune Motor
Parameters
00: Disable
01: Auto tune for R1
02: Auto tune for R1 + No Load testing
00
Pr.104 R1
value
00 to 65535 m
Ω
00
Pr.105 Control
Mode
00: V/F Control
01: Sensor-less Control
00
Pr.106
Rated Slip
0.00 to 10.00 Hz
3.00
Pr.107
Vector Voltage Filter
5 to 9999 (per 2ms)
10
Pr.108
Vector Slip
Compensation Filter
25 to 9999 (per 2ms)
50
Pr.109
Selection for Zero
Speed Control
00: No output
01: Control by DC voltage
00
Summary of Contents for VFD-M Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 12: ...Chapter 1 Introduction Revision May 2008 ME14 SW V3 04 1 3 1 1 4 External Parts and Labels ...
Page 17: ...Chapter 1 Introduction 1 8 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 21: ...Chapter 2 Installation and Wiring 2 4 Revision May 2008 ME14 SW V3 04 Good Not allowed ...
Page 121: ...Chapter 4 Parameters 4 86 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 149: ...Appendix B Accessories B 4 Revision May 2008 ME14 SW V3 04 ...