Chapter 4 Parameters
|
Revision May 2008, ME14, SW V3.04
4-31
Input
Power
Allowable Max. Power Loss Time
Output
Power
Output
Voltage
Pr.33
Speed search starts with
the Master Frequency
Pr.32=1
Baseblock
Time
Pr.34
speed synchronization
detection
speed search
Allowable Max. power loss time
Pr.33
Speed search starts with
minimum output frequency
Pr.32=2
Baseblock
Time
Pr.34
Pr.36
Upper Bound of Output Frequency
Unit: 0.1Hz
Settings 0.10 Hz to 400.0 Hz
Factory Setting: 400
The Upper/Lower Bounds help prevent operation error and machine damage.
If the Upper Bound of Output Frequency is 50Hz and the Maximum Output Frequency is 60Hz,
the Maximum Output Frequency will be limited to 50Hz.
Setting of this parameter must be equal to or greater than the Lower Bound of Output
Frequency (Pr.37).
Pr.37
Lower Bound of Output Frequency
Unit: 0.1Hz
Settings 0.00 Hz to 400.0 Hz
Factory Setting: 0 Hz
Setting of this parameter must be equal to or less than the Upper Bound of Output Frequency
If the Lower Bound of Output Frequency is 10Hz, and the Minimum Output Frequency (Pr.08)
is set at 1.0Hz, then any command frequency between 1-10Hz will generate a 10Hz output
from the drive.
output frequency
Pr.36
Pr.37
Input Freq.
Summary of Contents for VFD-M Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 12: ...Chapter 1 Introduction Revision May 2008 ME14 SW V3 04 1 3 1 1 4 External Parts and Labels ...
Page 17: ...Chapter 1 Introduction 1 8 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 21: ...Chapter 2 Installation and Wiring 2 4 Revision May 2008 ME14 SW V3 04 Good Not allowed ...
Page 121: ...Chapter 4 Parameters 4 86 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 149: ...Appendix B Accessories B 4 Revision May 2008 ME14 SW V3 04 ...