Chapter 4 Parameters
|
Revision May 2008, ME14, SW V3.04
4-43
Pr.47
Desired Frequency Attained
Unit: 0.1Hz
Settings 0.00 to 400.0 Hz
Factory Setting: 0.00
This parameter allows monitoring a certain frequency and then activates one of the Multi-
function output terminals (Pr.45 or Pr.46 set to 8) when that frequency is achieved.
Desired Freq.
Detection
range
-2Hz
Detection
range
+
-
4Hz
Detection range
+
-
2Hz
Time
Freq.
Max. Output
Freq.
ON
ON
OFF
OFF
OFF
OFF
Preset Freq.
Attained
Indication
Pr.45 to
Pr.46
Desired Freq.
Attained
Indication
Pr.45 & Pr.46
Desired Freq. Attained & Preset Freq. Attained
Pr.47
Pr.48
Adjust Bias of External Input Frequency
Unit: 0.1Hz
Settings 0.00 to 200.0%
Factory Setting: 0.00 Hz
This parameter provides a frequency offset when the source of frequency command is the
analog input.
Pr.49
Potentiometer Bias Polarity
Factory Setting: 00
Settings
00
Positive
Bias
01
Negative
Bias
This parameter sets the potentiometer Bias Frequency to be positive or negative.
Pr.50
Potentiometer Frequency Gain
Unit: 1%
Settings 0.10 to 200.0%
Factory Setting: 100.0
This parameter sets the ratio of analog input vs frequency output.
Pr.51
Potentiometer Reverse Motion Enable
Factory Setting: 00
Settings 00 Reverse Motion Disabled in negative bias
01 Reverse Motion Enabled in negative bias
Summary of Contents for VFD-M Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 12: ...Chapter 1 Introduction Revision May 2008 ME14 SW V3 04 1 3 1 1 4 External Parts and Labels ...
Page 17: ...Chapter 1 Introduction 1 8 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 21: ...Chapter 2 Installation and Wiring 2 4 Revision May 2008 ME14 SW V3 04 Good Not allowed ...
Page 121: ...Chapter 4 Parameters 4 86 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Page 149: ...Appendix B Accessories B 4 Revision May 2008 ME14 SW V3 04 ...