Chapter 6 Control Modes of Operation
|
ASDA-AB Series
Revision January 2009
6-41
Example: P0-03 = 01(CH1 is speed analog output)
Motor rotation speed = (Max. rotation speed × V1/8) × P1-04/100, when the output voltage value
of CH1 is V1.
P1 - 03
AOUT Pulse Output Polarity Setting
Communication Addr.: 0103H
Default: 0
Related Section:
Applicable Control Mode: P/S/T
Section 3.3.3
Unit: N/A
Range: 0 ~ 1
Settings:
not used
A
B
Monitor analog output polarity
•
A=0: MON1(+), MON2(+)
•
A=1: MON1(+), MON2(-)
•
A=2: MON1(-), MON2(+)
•
A=3: MON1(-), MON2(-)
Pulse output polarity
•
B=0: Forward output
•
B=1: Reverse output
P1 - 04
Analog Monitor Output Proportion 1 (CH1)
Communication Addr.: 0104H
Default: 100
Related Section:
Applicable Control Mode: P/S/T
Section 6.4.4
Unit: % (full scale)
Range: 0 ~ 100
P1 - 05
Analog Monitor Output Proportion 2 (CH2)
Communication Addr.: 0105H
Default: 100
Related Section:
Applicable Control Mode: P/S/T
Section 6.4.4
Unit: % (full scale)
Range: 0~100
P4 - 20
DOF1
Analog Monitor Output Drift Adjustment (CH1)
Communication Addr.: 0414H
Default: Factory setting
Related Section:
Applicable Control Mode: P/S/T
Section 6.4.4
Unit: mV
Range: -800~800
This parameter cannot be reset.
Summary of Contents for AC Servo Drive ASDA-AB
Page 1: ......
Page 13: ...Table of Contents ASDA AB Series Revision January 2009 This page intentionally left blank...
Page 85: ...Chapter 5 Trial Run and Tuning Procedure ASDA AB Series 5 8 Revision January 2009...
Page 246: ...Chapter 8 MODBUS Communications ASDA AB Series Revision January 2009 8 3 Cable Connection...
Page 307: ...Chapter 12 Application Examples ASDA AB Series 12 10 Revision January 2009...