Chapter 7 Servo Parameters
|
ASDA-AB Series
Revision January 2009
7-33
P1 - 13
TQ2
2nd Torque Command or Limit
Communication Addr.: 010DH
Default: 100
Related Section:
Applicable Control Mode: T, P/S
Section 6.4.1
Unit: %
Range: -300 ~ +300
Settings:
2nd Torque Command
In Torque mode, this parameter is used to set torque 2 of internal torque command.
2nd Torque Limit
In Position and Speed mode, this parameter is used to set torque limit 2 of internal torque
command.
Digital output signal TQL is activated when the drive has detected that the motor has reached
the torques limits set by either the parameters P1-12 ~ P1-14 of via an external analog voltage.
P1 - 14
TQ3
3rd Torque Command or Limit
Communication Addr.: 010EH
Default: 100
Related Section:
Applicable Control Mode: T, P/S
Section 6.4.1
Unit: %
Range: -300 ~ +300
Settings:
3rd Speed Command
In Torque mode, this parameter is used to set torque 3 of internal torque command.
3rd Speed Limit
In Position and Speed mode, this parameter is used to set torque limit 3 of internal torque
command.
Digital output signal TQL is activated when the drive has detected that the motor has reached
the torques limits set by either the parameters P1-12 ~ P1-14 of via an external analog voltage.
P1 - 15
PO1H 1st Position Command for Rotation
Communication Addr.: 010FH
Default: 0
Related Section:
Applicable Control Mode: Pr
Section 6.2.2
Unit: rev
Range: -30000 ~ +30000
Settings:
This parameter is used to set rotation cycle number of internal position 1.
Summary of Contents for AC Servo Drive ASDA-AB
Page 1: ......
Page 13: ...Table of Contents ASDA AB Series Revision January 2009 This page intentionally left blank...
Page 85: ...Chapter 5 Trial Run and Tuning Procedure ASDA AB Series 5 8 Revision January 2009...
Page 246: ...Chapter 8 MODBUS Communications ASDA AB Series Revision January 2009 8 3 Cable Connection...
Page 307: ...Chapter 12 Application Examples ASDA AB Series 12 10 Revision January 2009...