[14]
Above
current, high
The motor current is higher than set in
[15]
Out of speed
range
The output speed is outside the range set in
and
[16]
Below speed,
low
The output speed is lower than the setting
in
.
[17]
Above speed,
high
The output speed is higher than the setting
in
.
[18]
Out of
feedback
range
The feedback is outside the range set in
and
.
[19]
Below
feedback low
The feedback is below the limit set in
.
[20]
Above
feedback high
The feedback is above the limit set in
.
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the motor,
the frequency converter, the brake resistor,
or the thermistor.
[25]
Reverse
Reversing. Logic ‘1’ =
relay activated, 24 V DC
when CW rotation of the motor. Logic ‘0’ =
relay not activated, no signal, when CCW
rotation of the motor.
[26]
Bus OK
Active communication (no time-out) via the
serial communication port.
[27]
Torque limit
and stop
Use in performing a coasting stop and in
torque limit condition. If the frequency
converter has received a stop signal and is at
the torque limit, the signal is Logic ‘0’.
[28]
Brake, no
warning
The brake is active and there are no
warnings.
[29]
Brake ready,
no fault
The brake is ready for operation and there
are no faults.
[30]
Brake fault
(IGBT)
The output is Logic ‘1’ when the brake IGBT
is short-circuited. Use this function to
protect the frequency converter if there is a
fault on the brake modules. Use the output/
relay to cut out the main voltage from the
frequency converter.
[35]
External
Interlock
External Interlock function has been
activated via one of the digital inputs.
[40]
Out of ref
range
[41]
Below
reference low
[42]
Above
reference
high
[45]
Bus Ctrl
[46]
Bus Ctrl 1 if
timeout
[47]
Bus Ctrl 0 if
timeout
[55]
Pulse output
[60]
Comparator 0 See parameter group 13-1*. If Comparator 0
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[61]
Comparator 1 See parameter group 13-1*. If Comparator 2
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[62]
Comparator 2 See parameter group 13-1*. If Comparator 2
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[63]
Comparator 3 See parameter group 13-1*. If Comparator 3
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[64]
Comparator 4 See parameter group 13-1*. If Comparator 4
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[65]
Comparator 5 See parameter group 13-1*. If Comparator 5
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[70]
Logic Rule 0
See parameter group 13-4*. If Logic Rule 0 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[71]
Logic Rule 1
See parameter group 13-4*. If Logic Rule 1 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[72]
Logic Rule 2
See parameter group 13-4*. If Logic Rule 2 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[73]
Logic Rule 3
See parameter group 13-4*. If Logic Rule 3 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[74]
Logic Rule 4
See parameter group 13-4*. If Logic Rule 4 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[75]
Logic Rule 5
See parameter group 13-4*. If Logic Rule 5 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[80]
SL Digital
Output A
See
. The input will
go high whenever the Smart Logic Action
[38]
Set dig. out. A high
is executed. The input
will go low whenever the Smart Logic Action
[32] Set dig. out. A low is executed.
[81]
SL Digital
Output B
See
. The input will
go high whenever the Smart Logic Action
[39]
Set dig. out. Bhigh
is executed. The input
will go low whenever the Smart Logic Action
[33]
Set dig. out. B low
is executed.
[82]
SL Digital
Output C
See
. The input will
go high whenever the Smart Logic Action
[40]
Set dig. out. C high
is executed. The input
will go low whenever the Smart Logic Action
[34]
Set dig. out. C low
is executed.
[83]
SL Digital
Output D
See
. The input will
go high whenever the Smart Logic Action
[41]
Set dig. out. D
high is executed. The
input will go low whenever the Smart Logic
Action [35]
Set dig. out. D low
is executed.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark