5.1.20 22-** Application Functions
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
22-0* Miscellaneous
22-00 External Interlock Delay
0 s
All set-ups
TRUE
0
Uint16
22-01 Power Filter Time
0.50 s
2 set-ups
TRUE
-2
Uint16
22-2* No-Flow Detection
22-20 Low Power Auto Set-up
[0] Off
All set-ups
FALSE
-
Uint8
22-21 Low Power Detection
[0] Disabled
All set-ups
TRUE
-
Uint8
22-22 Low Speed Detection
[0] Disabled
All set-ups
TRUE
-
Uint8
22-23 No-Flow Function
[0] Off
All set-ups
TRUE
-
Uint8
22-24 No-Flow Delay
10 s
All set-ups
TRUE
0
Uint16
22-26 Dry Pump Function
[0] Off
All set-ups
TRUE
-
Uint8
22-27 Dry Pump Delay
10 s
All set-ups
TRUE
0
Uint16
22-3* No-Flow Power Tuning
22-30 No-Flow Power
0.00 kW
All set-ups
TRUE
1
Uint32
22-31 Power Correction Factor
100 %
All set-ups
TRUE
0
Uint16
22-32 Low Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
22-33 Low Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
22-34 Low Speed Power [kW]
ExpressionLimit
All set-ups
TRUE
1
Uint32
22-35 Low Speed Power [HP]
ExpressionLimit
All set-ups
TRUE
-2
Uint32
22-36 High Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
22-37 High Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
22-38 High Speed Power [kW]
ExpressionLimit
All set-ups
TRUE
1
Uint32
22-39 High Speed Power [HP]
ExpressionLimit
All set-ups
TRUE
-2
Uint32
22-4* Sleep Mode
22-40 Minimum Run Time
10 s
All set-ups
TRUE
0
Uint16
22-41 Minimum Sleep Time
10 s
All set-ups
TRUE
0
Uint16
22-42 Wake-up Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
22-43 Wake-up Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
22-44 Wake-up Ref./FB Difference
10 %
All set-ups
TRUE
0
Int8
22-45 Setpoint Boost
0 %
All set-ups
TRUE
0
Int8
22-46 Maximum Boost Time
60 s
All set-ups
TRUE
0
Uint16
22-5* End of Curve
22-50 End of Curve Function
[0] Off
All set-ups
TRUE
-
Uint8
22-51 End of Curve Delay
10 s
All set-ups
TRUE
0
Uint16
22-6* Broken Belt Detection
22-60 Broken Belt Function
[0] Off
All set-ups
TRUE
-
Uint8
22-61 Broken Belt Torque
10 %
All set-ups
TRUE
0
Uint8
22-62 Broken Belt Delay
10 s
All set-ups
TRUE
0
Uint16
22-7* Short Cycle Protection
22-75 Short Cycle Protection
[0] Disabled
All set-ups
TRUE
-
Uint8
22-76 Interval between Starts
Param. 2277
All set-ups
TRUE
0
Uint16
22-77 Minimum Run Time
0 s
All set-ups
TRUE
0
Uint16
22-78 Minimum Run Time Override
[0] Disabled
All set-ups
FALSE
-
Uint8
22-79 Minimum Run Time Override Value
0.000 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
22-8* Flow Compensation
22-80 Flow Compensation
[0] Disabled
All set-ups
TRUE
-
Uint8
22-81 Square-linear Curve Approximation
100 %
All set-ups
TRUE
0
Uint8
22-82 Work Point Calculation
[0] Disabled
All set-ups
TRUE
-
Uint8
22-83 Speed at No-Flow [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
22-84 Speed at No-Flow [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
Parameter Lists