13-52 SL Controller Action
Array [20]
Option:
Function:
[41]
Set digital out D
high
Any output with ‘digital output 4’
selected is high (closed).
[42]
Set digital out E
high
Any output with ‘digital output 5’
selected is high (closed).
[43]
Set digital out F
high
Any output with ‘digital output 6’
selected is high (closed).
[60]
Reset Counter A
Resets Counter A to zero.
[61]
Reset Counter B
Resets Counter A to zero.
[70]
Start Timer 3
Starts timer 3, see
for further description.
[71]
Start Timer 4
Starts timer 4, see
for further description.
[72]
Start Timer 5
Starts timer 5, see
for further description.
[73]
Start Timer 6
Starts timer 6, see
for further description.
[74]
Start Timer 7
Starts timer 7, see
for further description.
[80]
Sleep Mode
[90]
Set ECB Bypass
Mode
[91]
Set ECB Drive
Mode
[100] Reset Alarms