0-20 Display Line 1.1 Small
Option:
Function:
[1668]
Pulse Input #33
[Hz]
Actual value of the frequency applied
at terminal 33 as a pulse input.
[1669]
Pulse Output #27
[Hz]
Actual value of pulses applied to
terminal 27 in digital output mode.
[1670]
Pulse Output #29
[Hz]
Actual value of pulses applied to
terminal 29 in digital output mode.
[1671]
Relay Output [bin] View the setting of all relays.
[1672]
Counter A
View the present value of Counter A.
[1673]
Counter B
View the present value of Counter B.
[1675]
Analog In X30/11
Actual value of the signal on input
X30/11 (General Purpose I/O Card.
Option)
[1676]
Analog In X30/12
Actual value of the signal on input
X30/12 (General Purpose I/O Card.
Optional)
[1677]
Analog Out X30/8
[mA]
Actual value at output X30/8
(General Purpose I/O Card. Optional)
Use
to
select the variable to be shown.
[1680]
Fieldbus CTW 1
Control word (CTW) received from
the Bus Master.
[1682]
Fieldbus REF 1
Main reference value sent with
control word via the serial communi-
cations network e.g. from the BMS,
PLC or other master controller.
[1684]
Comm. Option
STW
Extended fieldbus communication
option status word.
[1685]
FC Port CTW 1
Control word (CTW) received from
the Bus Master.
[1686]
FC Port REF 1
Status word (STW) sent to the Bus
Master.
[1690]
Alarm Word
One or more alarms in a Hex code
(used for serial communications)
[1691]
Alarm Word 2
One or more alarms in a Hex code
(used for serial communications)
[1692]
Warning Word
One or more warnings in a Hex code
(used for serial communications)
[1693]
Warning Word 2
One or more warnings in a Hex code
(used for serial communications)
[1694]
Ext. Status Word
One or more status conditions in a
Hex code (used for serial communi-
cations)
[1695]
Ext. Status Word 2 One or more status conditions in a
Hex code (used for serial communi-
cations)
[1696]
Maintenance
Word
The bits reflect the status for the
programmed Preventive
0-20 Display Line 1.1 Small
Option:
Function:
Maintenance Events in parameter
group 23-1*
[1830]
Analog Input
X42/1
Shows the value of the signal applied
to terminal X42/1 on the Analog I/O
card.
[1831]
Analog Input
X42/3
Shows the value of the signal applied
to terminal X42/3 on the Analog I/O
card.
[1832]
Analog Input
X42/5
Shows the value of the signal applied
to terminal X42/5 on the Analog I/O
card.
[1833]
Analog Out X42/7
[V]
Shows the value of the signal applied
to terminal X42/7 on the Analog I/O
card.
[1834]
Analog Out X42/9
[V]
Shows the value of the signal applied
to terminal X42/9 on the Analog I/O
card.
[1835]
Analog Out
X42/11 [V]
Shows the value of the signal applied
to terminal X42/11 on the Analog I/O
card.
[1836]
Analog Input
X48/2 [mA]
[1837]
Temp. Input X48/4
[1838]
Temp. Input X48/7
[1839]
Temp. Input
X48/10
[1850]
Sensorless
Readout [unit]
[2117]
Ext. 1 Reference
[Unit]
The value of the reference for
extended Closed Loop Controller 1
[2118]
Ext. 1 Feedback
[Unit]
The value of the feedback signal for
extended Closed Loop Controller 1
[2119]
Ext. 1 Output [%]
The value of the output from
extended Closed Loop Controller 1
[2137]
Ext. 2 Reference
[Unit]
The value of the reference for
extended Closed Loop Controller 2
[2138]
Ext. 2 Feedback
[Unit]
The value of the feedback signal for
extended Closed Loop Controller 2
[2139]
Ext. 2 Output [%]
The value of the output from
extended Closed Loop Controller 2
[2157]
Ext. 3 Reference
[Unit]
The value of the reference for
extended Closed Loop Controller 3
[2158]
Ext. 3 Feedback
[Unit]
The value of the feedback signal for
extended Closed Loop Controller 3
[2159]
Ext. 3 Output [%]
The value of the output from
extended Closed Loop Controller 3
[2230]
No-Flow Power
The calculated No Flow Power for the
actual operating speed
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®