10-13 Warning Parameter
Range:
Function:
0
*
[0 - 65535 ] View a DeviceNet-specific Warning word. One
bit is assigned to every warning. Please refer to
the DeviceNet Operating Instructions (MG.
33.DX.YY) for further information.
Bit:
Meaning:
0
Bus not active
1
Explicit connection timeout
2
I/O connection
3
Retry limit reached
4
Actual is not updated
5
CAN bus off
6
I/O send error
7
Initialisation error
8
No bus supply
9
Bus off
10
Error passive
11
Error warning
12
Duplicate MAC ID Error
13
RX queue overrun
14
TX queue overrun
15
CAN overrun
10-14 Net Reference
Read only from LCP
Option: Function:
Select the reference source in Instance 21/71 and 20/70.
[0]
*
Off Enables reference via analog/digital inputs.
[1]
On Enables reference via the fieldbus.
10-15 Net Control
Read only from LCP
Option: Function:
Select the control source in Instance 21/71 and 20/70.
[0]
*
Off Enables control via analog/digital inputs.
[1]
On Enable control via the fieldbus.
3.11.4 10-2* COS Filters
10-20 COS Filter 1
Range:
Function:
0
*
[0 - 65535 ] Enter the value for COS Filter 1 to set up the
filter mask for the Status Word. When operating
in COS (Change-Of-State), this function filters
out bits in the Status Word that should not be
sent if they change.
10-21 COS Filter 2
Range:
Function:
0
*
[0 - 65535 ] Enter the value for COS Filter 2, to set up the
filter mask for the Main Actual Value. When
operating in COS (Change-Of-State), this
function filters out bits in the Main Actual Value
that should not be sent if they change.
10-22 COS Filter 3
Range:
Function:
0
*
[0 - 65535 ] Enter the value for COS Filter 3, to set up the
filter mask for PCD 3. When operating in COS
(Change-Of-State), this function filters out bits
in PCD 3 that should not be sent if they change.
10-23 COS Filter 4
Range:
Function:
0
*
[0 - 65535 ] Enter the value for COS Filter 4 to set up the
filter mask for PCD 4. When operating in COS
(Change-Of-State), this function filters out bits
in PCD 4 that should not be sent if they change.
3.11.5 10-3* Parameter Access
Parameter group providing access to indexed parameters
and defining programming set-up.
10-31 Store Data Values
Option:
Function:
Parameter values changed via DeviceNet are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values will be
retained at power-down.
[0] Off
Deactivates the non-volatile storage function.
[1] Store all
setups
Stores all parameter values from the active set-up
in the non-volatile memory. The selection returns
to Off [0] when all values have been stored.
[2] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
10-33 Store Always
Option: Function:
[0] Off Deactivates non-volatile storage of data.
[1] On Stores parameter data received via DeviceNet in EEPROM
non-volatile memory as default.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
89