[66] Sleep Mode
Forces frequency converter into Sleep Mode
(see par. 22-4*). Reacts on the rising edge of
signal applied!
[68] Timed Actions
Disabled
Timed actions are disabled. See parameter
group
23-0* Timed Actions
.
[69] Constant OFF
Timed Actions
are set for Constant OFF. See
parameter group
23-0* Timed Actions
.
[70] Constant ON
Timed Actions
are set for Constant ON. See
parameter group
23-0* Timed Actions
.
[78] Reset
Preventive
Maintenance
Word
Resets all data in
to
0.
5-10 Terminal 18 Digital Input
Same options and functions as 5-1*, except for
Pulse input
.
Option:
Function:
[8]
*
Start
5-11 Terminal 19 Digital Input
Same options and functions as 5-1*, except for
Pulse input
.
Option:
Function:
[0]
*
No operation
5-12 Terminal 27 Digital Input
Option:
Function:
[2]
*
Coast inverse Functions are described under 5-1*
Digital
Inputs
5-13 Terminal 29 Digital Input
Option:
Function:
Select the function from the available digital input
range and the additional options [60], [61], [63] and
[64]. Counters are used in Smart Logic Control
functions.This parameter is available for FC 302 only.
[14]
*
Jog Functions are described under 5-1*
Digital Inputs
5-14 Terminal 32 Digital Input
Option:
Function:
[0]
*
No Operation Same options and functions as par. 5-1*
Digital Inputs
, except for
Pulse input
.
5-15 Terminal 33 Digital Input
Option:
Function:
[0]
*
No Operation Same options and functions as par. group 5-1*
Digital Inputs
.
5-16 Terminal X30/2 Digital Input
This parameter is active when option module MCB 101 is installed
in the frequency converter. Same options and functions as par.
group 5-1* except for
Pulse input
[32].
Option:
Function:
[0]
*
No operation
5-17 Terminal X30/3 Digital Input
This parameter is active when option module MCB 101 is installed
in the frequency converter. Same options and functions as par.
group 5-1* except for
Pulse input
[32].
Option:
Function:
[0]
*
No operation
5-18 Terminal X30/4 Digital Input
This parameter is active when option module MCB 101 is installed
in the frequency converter. Same options and functions as par.
group 5-1* except for
Pulse input
[32].
Option:
Function:
[0]
*
No operation
3.7.4 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in
and set the I/O function
for terminal 29 in
. These parameters
cannot be adjusted while the motor is running.
The digital outputs can be programmed
with these functions:
[0]
No operation
Default for all digital outputs and relay
outputs
[1]
Control ready The control board receives supply voltage.
[2]
Drive ready
The frequency converter is ready for
operation and applies a supply signal on the
control board.
[3]
Drive ready /
remote
control
The frequency converter is ready for
operation and is in Auto On mode.
[4]
Stand-by / no
warning
The frequency converter is ready for
operation. No start or stop command is been
given (start/disable). There are no warnings.
[5]
Running
The motor is running.
[6]
Running / no
warning
The output speed is higher than the speed
set in
1-81 Min Speed for Function at Stop
. The motor is running and there are no
warnings.
[8]
Run on
reference / no
warning
The motor runs at reference speed.
[9]
Alarm
An alarm activates the output. There are no
warnings.
[10]
Alarm or
warning
An alarm or a warning activates the output.
[11]
At torque
limit
The torque limit set in
or par. 4-17 has been exceeded.
[12]
Out of current
range
The motor current is outside the range set in
[13]
Below current,
low
The motor current is lower than set in
.
Parameter Description
VLT
®
HVAC Drive Programming Guide
60