5.1.6 4-** Limits / Warnings
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
4-1* Motor Limits
4-10
Motor Speed Direction
[2] Both directions
All set-ups
FALSE
-
Uint8
4-11
Motor Speed Low Limit [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-12
Motor Speed Low Limit [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-13
Motor Speed High Limit [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-14
Motor Speed High Limit [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-16
Torque Limit Motor Mode
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-17
Torque Limit Generator Mode
100.0 %
All set-ups
TRUE
-1
Uint16
4-18
Current Limit
ExpressionLimit
All set-ups
TRUE
-1
Uint32
4-19
Max Output Frequency
ExpressionLimit
All set-ups
FALSE
-1
Uint16
4-5* Adj. Warnings
4-50
Warning Current Low
0.00 A
All set-ups
TRUE
-2
Uint32
4-51
Warning Current High
Param. 1637
All set-ups
TRUE
-2
Uint32
4-52
Warning Speed Low
0 RPM
All set-ups
TRUE
67
Uint16
4-53
Warning Speed High
Param. 413
All set-ups
TRUE
67
Uint16
4-54
Warning Reference Low
-999999.999 N/A
All set-ups
TRUE
-3
Int32
4-55
Warning Reference High
999999.999 N/A
All set-ups
TRUE
-3
Int32
4-56
Warning Feedback Low
-999999.999 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
4-57
Warning Feedback High
999999.999 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
4-58
Missing Motor Phase Function
[2] Trip 1000 ms
All set-ups
TRUE
-
Uint8
4-6* Speed Bypass
4-60
Bypass Speed From [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-61
Bypass Speed From [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-62
Bypass Speed To [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-63
Bypass Speed To [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-64
Semi-Auto Bypass Set-up
[0] Off
All set-ups
FALSE
-
Uint8
Parameter Lists
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
203