0-20 Display Line 1.1 Small
Option:
Function:
and
.
[1610]
Power [kW]
Actual power consumed by the
motor in kW.
[1611]
Power [hp]
Actual power consumed by the
motor in HP.
[1612]
Motor Voltage
Voltage supplied to the motor.
[1613]
Frequency
Motor frequency, i.e. the output
frequency from the frequency
converter in Hz.
[1614]
Motor Current
Phase current of the motor measured
as effective value.
[1615]
Frequency [%]
Motor frequency, i.e. the output
frequency from the frequency
converter in percent.
[1616]
Torque [Nm]
Present motor load as a percentage
of the rated motor torque.
[1617]
Speed [RPM]
Motor speed reference. Actual speed
will depend on slip compensation
being used (compensation set in
). If not used,
actual speed will be the value read in
the display minus motor slip.
[1618]
Motor Thermal
Thermal load on the motor,
calculated by the ETR function. See
also parameter group 1-9* Motor
Temperature.
[1622]
Torque [%]
Shows the actual torque produced, in
percentage.
[1626]
Power Filtered
[kW]
[1627]
Power Filtered
[hp]
[1630]
DC Link Voltage
Intermediate circuit voltage in the
frequency converter.
[1632]
Brake Energy /s
Present brake power transferred to
an external brake resistor.
Stated as an instantaneous value.
[1633]
Brake Energy /2
min
Brake power transferred to an
external brake resistor. The mean
power is calculated continuously for
the most recent 120 seconds.
[1634]
Heatsink Temp.
Present heat sink temperature of the
frequency converter. The cut-out
limit is 95 ± 5
°
C; cutting back in
occurs at 70 ± 5
°
C.
[1635]
Inverter Thermal
Percentage load of the inverters
0-20 Display Line 1.1 Small
Option:
Function:
[1636]
Inv. Nom. Current Nominal current of the frequency
converter
[1637]
Inv. Max. Current
Maximum current of the frequency
converter
[1638]
SL Controller State State of the event executed by the
control
[1639]
Control Card
Temp.
Temperature of the control card.
[1643]
Timed Actions
Status
See parameter group
23-0* Timed
Actions
.
[1650]
External Reference Sum of the external reference as a
percentage, i.e. the sum of analog/
pulse/bus.
[1652]
Feedback [Unit]
Reference value from programmed
digital input(s).
[1653]
Digi Pot Reference View the contribution of the digital
potentiometer to the actual
reference Feedback.
[1654]
Feedback 1 [Unit]
View the value of Feedback 1. See
also par. 20-0*.
[1655]
Feedback 2 [Unit]
View the value of Feedback 2. See
also par. 20-0*.
[1656]
Feedback 3 [Unit]
View the value of Feedback 3. See
also par. 20-0*.
[1658]
PID Output [%]
Returns the Drive Closed Loop PID
controller output value in percent.
[1660]
Digital Input
Displays the status of the digital
inputs. Signal low = 0; Signal high =
1.
Regarding order, see
. Bit 0 is at the extreme right.
[1661]
Terminal 53
Switch Setting
Setting of input terminal 53. Current
= 0; Voltage = 1.
[1662]
Analog Input 53
Actual value at input 53 either as a
reference or protection value.
[1663]
Terminal 54
Switch Setting
Setting of input terminal 54. Current
= 0; Voltage = 1.
[1664]
Analog Input 54
Actual value at input 54 either as
reference or protection value.
[1665]
Analog Output 42
[mA]
Actual value at output 42 in mA. Use
to select the
variable to be represented by output
42.
[1666]
Digital Output
[bin]
Binary value of all digital outputs.
[1667]
Pulse Input #29
[Hz]
Actual value of the frequency applied
at terminal 29 as a pulse input.
Parameter Description
VLT
®
HVAC Drive Programming Guide