6-44 Term. X30/12 Low Ref./Feedb. Value
Range:
Function:
0.000
*
[-999999.999 -
999999.999 ]
Sets the analog output scaling
value to correspond to the low
voltage value set in
.
6-45 Term. X30/12 High Ref./Feedb. Value
Range:
Function:
100.000
*
[-999999.999 -
999999.999 ]
Sets the analog input scaling
value to correspond to the high
voltage value set in
6-46 Term. X30/12 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10.000
s]
A 1
st
order digital low pass filter time
constant for suppressing electrical noise
on terminal X30/12.
6-46 Term. X30/12 Filter Time Constant
cannot be changed while the motor is
running.
6-47 Term. X30/12 Live Zero
Option:
Function:
This parameter makes it possible to disable the Live
Zero monitoring. E.g. to be used if the analog
outputs are used as part of a decentral I/O system
(e.g. when not part of any frequency converter
related control functions, but feeding a Building
Management System with data)
[0]
*
Disabled
[1]
Enabled
3.8.6 6-5* Analog Output 1
Parameters for configuring the scaling and limits for analog
output 1, i.e. Terminal 42. Analog outputs are current
outputs: 0/4 – 20 mA. Common terminal (terminal 39) is the
same terminal and has the same electrical potential for
analog common and digital common connection. Resolution
on analog output is 12 bit.
6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42 as
an analog current output. A motor
current of 20 mA corresponds to I
max
.
[0]
*
No operation
[100]
Output freq. 0-100 0 - 100 Hz, (0-20 mA)
[101]
Reference Min-Max Minimum reference - Maximum
reference, (0-20 mA)
6-50 Terminal 42 Output
Option:
Function:
[102]
Fe-200%
-200% to +200% of
, (0-20 mA)
[103]
Motor cur. 0-Imax
0 - Inverter Max. Current (
), (0-20 mA)
[104]
Torque 0-Tlim
0 - Torque limit (
), (0-20 mA)
[105]
Torque 0-Tnom
0 - Motor rated torque, (0-20 mA)
[106]
Power 0-Pnom
0 - Motor rated power, (0-20 mA)
[107]
*
Speed 0-HighLim
0 - Speed High Limit (
and
), (0-20 mA)
[113]
Ext. Closed Loop 1 0 - 100%, (0-20 mA)
[114]
Ext. Closed Loop 2 0 - 100%, (0-20 mA)
[115]
Ext. Closed Loop 3 0 - 100%, (0-20 mA)
[130]
Out frq 0-100
4-20mA
0 - 100 Hz
[131]
Reference 4-20mA Minimum Reference - Maximum
Reference
[132]
Feedback 4-20mA
-200% to +200% of
[133]
Motor cur. 4-20mA 0 - Inverter Max. Current (
)
[134]
Torq.0-lim 4-20 mA 0 - Torque limit (
)
[135]
Torq.0-nom
4-20mA
0 - Motor rated torque
[136]
Power 4-20mA
0 - Motor rated power
[137]
Speed 4-20mA
0 - Speed High Limit (4-13 and 4-14)
[139]
Bus ctrl.
0 - 100%, (0-20 mA)
[140]
Bus ctrl. 4-20 mA
0 - 100%
[141]
Bus ctrl t.o.
0 - 100%, (0-20 mA)
[142]
Bus ctrl t.o. 4-20mA 0 - 100%
[143]
Ext. CL 1 4-20mA
0 - 100%
[144]
Ext. CL 2 4-20mA
0 - 100%
[145]
Ext. CL 3 4-20mA
0 - 100%
NOTE
Values for setting the Minimum Reference is found in open
loop
and for closed loop
20-13 Minimum Reference/Feedb.
- values for maximum
reference for open loop is found in
3-03 Maximum Reference
and for closed loop
20-14 Maximum Reference/Feedb.
.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
71