2.1.13 Read-out and Programming of
Indexed Parameters
Parameters are indexed when placed in a rolling stack.
to
15-33 Alarm Log: Date and Time
contain a fault log which can be read out. Choose a
parameter, press [OK], and use the up/down navigation keys
to scroll through the value log.
Use
as another example:
Choose the parameter, press [OK], and use the up/down
navigation keys keys to scroll through the indexed values. To
change the parameter value, select the indexed value and
press [OK]. Change the value by using the up/down keys.
Press [OK] to accept the new setting. Press [CANCEL] to
abort. Press [Back] to leave the parameter.
2.1.14 Initialisation to Default Settings
Initialise the frequency converter to default settings in two
ways:
Recommended initialisation (via
1.
Select
2.
Press [OK]
3.
Select “initialisation”
4.
Press [OK]
5.
Cut off the mains supply and wait until the display
turns off.
6.
Reconnect the mains supply - the frequency
converter is now reset.
7.
Change
back to
Normal
Operation
.
NOTE
Resets parameters selected in Personal Menu with default
factory setting.
initialises all except:
14-50 RFI Filter
8-30 Protocol
8-31 Address
8-32 Baud Rate
8-35 Minimum Response Delay
8-36 Maximum Response Delay
8-37 Maximum Inter-Char Delay
15-00 Operating Hours
to
to
to
Manual initialisation
1.
Disconnect from mains and wait until the display turns off.
2a.
Press [Status] - [Main Menu] - [OK] at the same time while
power up for LCP 102, Graphical Display
2b.
Press [Menu] while power up for LCP 101, Numerical
Display
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed according to
default settings.
This procedure initialises all except:
;
NOTE
When you carry out manual initialisation, you also reset serial
communication,
and fault log settings.
Removes parameters selected in
.
NOTE
After initialisation and power cycling, the display will not
show any information until after a couple of minutes.
How to Programme
VLT
®
HVAC Drive Programming Guide
24