Line Power Supply 3 x 525–690V AC
P315
P400
P450
Typical Shaft output at 550V [kW]
250
315
355
Typical Shaft output at 575V [HP]
350
400
450
Typical Shaft output at 690V [kW]
315
400
450
Enclosure IP21
D2
D2
E1
Enclosure IP54
D2
D2
E1
Enclosure IP00
D4
D4
E2
Output current
130BA230.10
Continuous
(at 550V) [A]
360
418
470
Intermittent (60 sec overload)
(at 550V) [A]
396
460
517
Continuous
(at 575/690V) [A]
344
400
450
Intermittent (60 sec overload)
(at 575/690V) [A]
378
440
495
Continuous KVA
(at 550V) [KVA]
343
398
448
Continuous KVA
(at 575V) [KVA]
343
398
448
Continuous KVA
(at 690V) [KVA]
411
478
538
Max. input current
130BA229.10
Continuous
(at 550V) [A]
355
408
453
Continuous
(at 575V) [A]
339
390
434
Continuous
(at 690V) [A]
352
400
434
Max. cable size, line power, motor and
load share [mm
2
(AWG)]
2 x 150
(2 x 300 mcm)
2 x 150
(2 x 300 mcm)
4 x 240
(4 x 500 mcm)
Max. cable size, brake [mm
2
(AWG)]
2 x 150
(2 x 300 mcm)
2 x 150
(2 x 300 mcm)
2 x 185
(2 x 350 mcm)
Max. external pre-fuses [A]
1
500
550
700
Estimated power loss
at rated max. load [W, hp]
4)
, 600V
5493, 7.37
5852, 7.85
6132, 8.22
Estimated power loss
at rated max. load [W, hp]
4)
, 690V
5821, 7.81
6149, 8.25
6440, 8.64
Weight,
enclosure IP21, IP54 (lb [kg])
332.9 [151]
363.8 [165]
579.8 [263]
Weight,
enclosure IP00 (lb [kg])
304.2 [138]
332.9 [151]
487.2 [221]
Efficiency
4)
0.98
Output frequency
0–600 Hz
0–500 Hz
0–500 Hz
Heatsink overtemp. trip
230°F [110
°
C]
230°F [110
°
C]
230°F [110
°
C]
Power card ambient trip
140°F [60
°
C]
140°F [60
°
C]
154.4°F [68
°
C]
Table 8.12
General Specifications and ...
VLT
®
HVAC Drive Design Guide
8-12
MG11BB22 - VLT
®
is a registered Danfoss trademark
8
8