X44/ 1 and X44/ 2 are the thermistor inputs, X44/ 12 will
enable safe stop of the FC 102 (T-37) if the thermistor
values make it necessary and X44/ 10 will inform the FC
102 that a request for safe stop came from the MCB 112 in
order to ensure suitable alarm handling. One of the digital
Inputs of the FC 102 (or a DI of a mounted option) must
be set to PTC Card 1 [80] in order to use the information
from X44/ 10.
5-19 Terminal 37 Safe Stop
Terminal 37 Safe
Stop must be configured to the desired safe stop
functionality (default is Safe Stop Alarm).
MS 220 DA
11
10
20-28 VDC
10 mA
12
20-28 VDC
60 mA
co
m
ZIEHL
X44
12
13 18
19
27
29 32 33
20 37
3
NC
4
NC
5
NC
6
NC
7
NC
8
NC
9
NC
10
11
NC
12
1
T1
2
T2
T
P
T
P
PTC
M3~
130BA638.10
DO
Motor protection
MCB 112 PTC Thermistor Card
Option B
Reference for 10, 12
DO FOR SAFE ST
OP
T37
Code No.130B1137
Control Terminals of FC302
Figure 3.11
ATEX Certification with
The MCB 112 has been certified for ATEX which means
that the FC 102 together with the MCB 112 can now be
used with motors in potentially explosive atmospheres. See
the Instruction Manual for the MCB 112 for more
information.
ATmosphère EXplosive (ATEX)
Table 3.9
VLT
®
HVAC Drive Selection
VLT
®
HVAC Drive Design Guide
3-8