8.1.2 Line Power Supply 3 x 525–690V AC
Normal
overload
110%
for
1
minute
Size:
P11K
P15K
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Typical
Shaft
Output
[kW]
11
15
18.5
22
30
37
45
55
75
90
Typical
Shaft
Output
[HP]
at
575V
10
16.4
20.1
24
33
40
50
60
75
100
IP21
/
NEMA
1
B2
B2
B2
B2
B2
C2
C2
C2
C2
C2
IP55
/
NEMA
12
B2
B2
B2
B2
B2
C2
C2
C2
C2
C2
Output
current
130BA058.10
Continuous (3
x
525–550
V)
[A]
14
19
23
28
36
43
54
65
87
105
Intermittent (3
x
525–550
V)
[A]
15.4
20.9
25.3
30.8
39.6
47.3
59.4
71.5
95.7
115.5
Continuous (3
x
551–690
V)
[A]
13
18
22
27
34
41
52
62
83
100
Intermittent (3
x
551–690V)
[A]
14.3
19.8
24.2
29.7
37.4
45.1
57.2
68.2
91.3
110
Continuous
kVA
(550V
AC)
[kVA]
13.3
18.1
21.9
26.7
34.3
41
51.4
61.9
82.9
100
Continuous
kVA
(575V
AC)
[kVA]
12.9
17.9
21.9
26.9
33.8
40.8
51.8
61.7
82.7
99.6
Continuous
kVA
(690V
AC)
[kVA]
15.5
21.5
26.3
32.3
40.6
49
62.1
74.1
99.2
119.5
Max.
cable
size
(line
power,
motor,
brake)
[mm
2
]/[AWG]
2)
35 1/0
95 4/0
Max.
input
current
130BA057.10
Continuous (3
x
525–690
V)
[A]
15
19.5
24
29
36
49
59
71
87
99
Intermittent (3
x
525–690V)
[A]
16.5
21.5
26.4
31.9
39.6
53.9
64.9
78.1
95.7
108.9
Max.
pre-fuses
1)
[A]
63
63
63
63
80
100
125
160
160
160
Environment: Estimated
power
loss
at
rated
max.
load
[W,
hp]
4)
201,
0.27
285,
0.38
335,
0.45
375,
0.50
430,
0.58
592,
0.79
720,
0.97
880,
1.18
1200,
1.61
1440,
1.93
Weight: IP21
(lb
[kg])
59.5
[27]
59.5
[27]
59.5
[27]
59.5
[27]
59.5
[27]
143.3
[65]
143.3
[65]
143.3
[65]
143.3
[65]
143.3
[65]
IP55
(lb
[kg])
59.5
[27]
59.5
[27]
59.5
[27]
59.5
[27]
59.5
[27]
143.3
[65]
143.3
[65]
143.3
[65]
143.3
[65]
143.3
[65]
Efficiency
4)
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
1)
For
type
of
fuse
see
5.2.8
Fuses
2)
American
Wire
Gauge
3)
Measured
using
16
ft
[5
m]
shielded
motor
cables
at
rated
load
and
rated
frequency
4)
The
typical
power
loss
is
at
normal
load
conditions
and
expected
to
be
within
+/-
15%
(tolerance
relates
to
variety
in
voltage
and
cable
conditions).
Values
are
based
on
a
typical
motor
efficiency
(eff2/eff3
border
line).
Lower
efficiency
motors
will
also
add
to
the
power
loss
in
the
Adjustable
frequency
drive
and
vice
versa.
If
the
switching
frequency
is
raised
from
nominal,
the
power
losses
may
rise
significantly.
LCP
and
typical
control
card
power
consumptions
are
included.
Further
options
and
customer
load
may
add
up
to
0.04
hp
[30
Watts]
to
the
losses.
(Though
typically
only
0.005
hp
[4
Watts]
extra
for
a
fully
loaded
control
card
or
options
for
slot
A
or
slot
B,
each).
Although
measurements
are
made
with
state
of
the
art
equipment,
some
measurement
inaccuracy
must
be
allowed
for
(+/-
5%).
5)
Motor
and
line
cable:
300MCM/150mm
2
Table
8.10
Line
Power
Supply
3
x
525–690V
AC
General Specifications and ...
VLT
®
HVAC Drive Design Guide
8-10
MG11BB22 - VLT
®
is a registered Danfoss trademark
8
8