1.
Use a clamp from the accessory bag to connect
the shield to the Adjustable frequency drive
decoupling plate for control cables.
See section entitled
5.7.3 Grounding of Shielded/Armored
Control Cables
for the correct termination of control cables.
130BA681.10
Figure 5.26
5.2.14 Switches S201, S202, and S801
Switches S201 (A53) and S202 (A54) are used to select a
current (0–20 mA) or a voltage (0–10 V) configuration of
the analog input terminals 53 and 54 respectively.
Switch S801 (BUS TER.) can be used to enable termination
on the RS-485 port (terminals 68 and 69).
See
Figure 5.25
Default setting:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF
NOTE!
It is recommended to only change switch position at
power off.
130B
T310.10
1
2
N O
VLT
BUS TER.
OFF-ON
A53 A54
U- I U- I
Figure 5.27
5.3 Final Set-Up and Test
To test the set-up and ensure that the Adjustable
frequency drive is running, follow these steps.
Step 1. Locate the motor nameplate
The motor is either star- (Y) or delta-connected (
Δ
). This
information is located on the motor nameplate data.
Step 2. Enter the motor nameplate data in this parameter
list.
To access this list, first press the [QUICK MENU] key, then
select “Q2 Quick Set-up”.
1.
Motor Power [kW]
or Motor Power [HP]
1-20 Motor Power [kW]
1-21 Motor Power [HP]
2.
Motor Voltage
1-22 Motor Voltage
3.
Motor Frequency
1-23 Motor Frequency
4.
Motor Current
1-24 Motor Current
5.
Motor Nominal Speed
1-25 Motor Nominal
Speed
Table 5.30
How to Install
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
5-25