8.1.1 Line Power Supply High Power
Line Power Supply 3 x 380–480 VAC
P110
P132
P160
P200
P250
Typical Shaft output at 400 V
[kW]
110
132
160
200
250
Typical Shaft output at 460 V
[HP]
150
200
250
300
350
Enclosure IP21
D1
D1
D2
D2
D2
Enclosure IP54
D1
D1
D2
D2
D2
Enclosure IP00
D3
D3
D4
D4
D4
Output current
130BA230.10
Continuous
(at 400 V) [A]
212
260
315
395
480
Intermittent (60 sec overload)
(at 400 V) [A]
233
286
347
435
528
Continuous
(at 460/ 480 V) [A]
190
240
302
361
443
Intermittent (60 sec overload)
(at 460/480 V) [A]
209
264
332
397
487
Continuous KVA
(at 400 V) [KVA]
147
180
218
274
333
Continuous KVA
(at 460 V) [KVA]
151
191
241
288
353
Max. input current
130BA229.10
Continuous
(at 400 V) [A]
204
251
304
381
463
Continuous
(at 460/ 480 V) [A]
183
231
291
348
427
Max. cable size, line power
motor, brake and load share
[mm
2
(AWG
2)
)]
2 x 70
(2 x 2/0)
2 x 70
(2 x 2/0)
2 x 150
(2 x 300 mcm)
2 x 150
(2 x 300
mcm)
2 x 150
(2 x 300 mcm)
Max. external pre-fuses [A]
1
300
350
400
500
630
Estimated power loss
at rated max. load [W, hp]
4)
,
400 V
3234, 4.34
3782, 5.07
4213, 5.65
5119, 6.86
5893, 7.90
Estimated power loss
at rated max. load [W, hp]
4)
,
460 V
2947, 3.95
3665, 4.91
4063, 5.45
4652, 6.24
5634, 7.56
Weight,
enclosure IP21, IP 54 (lb [kg])
96
104
125
136
151
Weight,
enclosure IP00 (lb [kg])
82
91
112
123
138
Efficiency
4)
0.98
Output frequency
0–800 Hz
Heatsink overtemp. trip
194°F [90
°
C]
230°F [110
°
C]
230°F [110
°
C]
230°F [110
°
C] 230°F [110
°
C]
Power card ambient trip
140°F [60
°
C]
Table 8.7
General Specifications and ...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
8-7
8
8