5.1.4 Mechanical Mounting
All A, B and C enclosures allow side-by-side installation.
Exception: If a IP21 kit is used, there has to be a clearance
between the enclosures. For enclosures A2, A3, B3, B4 and
C3 the minimum clearance is 2 in [50 mm], for C4 it is 3 in
[75 mm].
For optimal cooling conditions, allow a free air passage
above and below the Adjustable frequency drive. See
Table 5.6
.
a
b
130BA419.10
Figure 5.1
Enclosure:
A2
A3
A5
B1
B2
B3
a/b (in
[mm])
3.94
[100]
3.94
[100]
3.94
[100]
7.87
[200]
7.87
[200]
7.87
[200]
Enclosure:
B4
C1
C2
C3
C4
a/b (in
[mm])
7.87
[200]
7.87
[200]
8.86
[225]
7.87
[200]
8.86
[225]
Table 5.6 Air Passage for Different Enclosures
1.
Drill holes in accordance with the measurements given.
2.
Provide screws suitable for the surface on which you want to mount the Adjustable frequency drive. Retighten all
four screws.
130BA219.10
A
130BA228.10
A
130BA392.10
IP66 Drive
Base
plate
Fibre
Washer
A
Table 5.7 When mounting enclosure sizes A5, B1, B2, B3, B4, C1, C2, C3 and C4 on a non-solid back wall,
the adjustable frequency drive must be provided with a backplate A due to insufficient cooling air over the heatsink.
How to Install
VLT
®
HVAC Drive Design Guide
5-6
MG11BB22 - VLT
®
is a registered Danfoss trademark