supply is needed, the jumpers are removed and the supply
is connected to terminals 100 and 101. A 5 Amp fuse
should be used for protection. In UL applications, this
should be a LittleFuse KLK-5 or equivalent.
5.4.7 Relay Output
Relay 1
•
Terminal 01: common
•
Terminal 02: normal open 240V AC
•
Terminal 03: normal closed 240V AC
Relay 2
•
Terminal 04: common
•
Terminal 05: normal open 400V AC
•
Terminal 06: normal closed 240V AC
Relay 1 and relay 2 are programmed in
5-40 Function Relay
,
5-41 On Delay, Relay
, and
5-42 Off Delay, Relay
.
Additional relay outputs can be added to the Adjustable
frequency drive by using option module MCB 105.
Figure 5.31
How to Install
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
5-29