Line
Power
Supply
3
x
380–480V
AC
-
Normal
overload
110%
for
1
minute
Adjustable
Frequency
Drive
Typical
Shaft
Output
[kW]
P11K
11
P15K
15
P18K
18.5
P22K
22
P30K
30
P37K
37
P45K
45
P55K
55
P75K
75
P90K
90
Typical
Shaft
Output
[hp]
at
460
V
15
20
25
30
40
50
60
75
100
125
IP20/Chassis
(B3+4
and
C3+4
may
be
converted
to
IP21
using
a
conversion
kit
(Please
contact
Danfoss)
B3
B3
B3
B4
B4
B4
C3
C3
C4
C4
IP21/NEMA
1
B1
B1
B1
B2
B2
C1
C1
C1
C2
C2
IP55/NEMA
12
B1
B1
B1
B2
B2
C1
C1
C1
C2
C2
IP66/NEMA
12
B1
B1
B1
B2
B2
C1
C1
C1
C2
C2
Output
current
130BA058.10
Continuous
(3
x
380–439V)
[A]
24
32
37.5
44
61
73
90
106
147
177
Intermittent
(3
x
380–439V)
[A]
26.4
35.2
41.3
48.4
67.1
80.3
99
117
162
195
Continuous
(3
x
440–480V)
[A]
21
27
34
40
52
65
80
105
130
160
Intermittent
(3
x
440–480V)
[A]
23.1
29.7
37.4
44
61.6
71.5
88
116
143
176
Continuous
kVA
(400V
AC)
[kVA]
16.6
22.2
26
30.5
42.3
50.6
62.4
73.4
102
123
Continuous
kVA
460V
AC)
[kVA]
16.7
21.5
27.1
31.9
41.4
51.8
63.7
83.7
104
128
Max.
cable
size:
(line
power,
motor,
brake)
[mm
2
/
AWG]
2)
10/7
35/2
50/1/0
(B4=35/2)
95/
4/0
120/
MCM250
With
line
power
disconnect
switch
included:
16/6
35/2
35/2
70/3/0
185/
kcmil350
Max.
input
current
130BA057.10
Continuous
(3
x
380–439V)
[A]
22
29
34
40
55
66
82
96
133
161
Intermittent
(3
x
380–-439V)
[A]
24.2
31.9
37.4
44
60.5
72.6
90.2
106
146
177
Continuous
(3
x
440–480V)
[A]
19
25
31
36
47
59
73
95
118
145
Intermittent
(3
x
440–480V)
[A]
20.9
27.5
34.1
39.6
51.7
64.9
80.3
105
130
160
Max.
pre-fuses
1)
[A]
63
63
63
63
80
100
125
160
250
250
Environment
Estimated
power
loss
at
rated
max.
load
[W,
hp]
4)
278,
0.37
392,
0.53
465,
0.62
525,
0.70
698,
0.94
739,
0.99
843,
1.13
1083,
1.45
1384,
1.86
1474,
1.98
Weight
enclosure
IP20
(lb
[kg])
26.5
[12]
26.5
[12]
26.5
[12]
51.8
[23.5]
51.8
[23.5]
51.8
[23.5]
77.2
[35]
77.2
[35]
164
[50]
164
[50]
Weight
enclosure
IP21
(lb
[kg])
9.1
[23]
9.1
[23]
9.1
[23]
59.5
[27]
59.5
[27]
99.2
[45]
99.2
[45]
99.2
[45]
143.3
[65]
143.3
[65]
Weight
enclosure
IP55
(lb
[kg])
9.1
[23]
9.1
[23]
9.1
[23]
59.5
[27]
59.5
[27]
99.2
[45]
99.2
[45]
99.2
[45]
143.3
[65]
143.3
[65]
Weight
enclosure
IP66
(lb
[kg])
9.1
[23]
9.1
[23]
9.1
[23]
59.5
[27]
59.5
[27]
99.2
[45]
99.2
[45]
99.2
[45]
143.3
[65]
143.3
[65]
Efficiency
3)
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.99
Table
8.4
Line
Power
Supply
3
x
380–480V
AC
General Specifications and ...
VLT
®
HVAC Drive Design Guide
8-4
MG11BB22 - VLT
®
is a registered Danfoss trademark
8
8