Line Power Supply 3 x 525–690V AC
P110
P132
P160
P200
P250
Typical Shaft output at 550V [kW]
90
110
132
160
200
Typical Shaft output at 575V [HP]
125
150
200
250
300
Typical Shaft output at 690V [kW]
110
132
160
200
250
Enclosure IP21
D1
D1
D1
D2
D2
Enclosure IP54
D1
D1
D1
D2
D2
Enclosure IP00
D2
D3
D3
D4
D4
Output current
130BA230.10
Continuous
(at 550V) [A]
137
162
201
253
303
Intermittent (60 sec overload)(at 550V) [A]
151
178
221
278
333
Continuous(at 575/690V) [A]
131
155
192
242
290
Intermittent (60 sec overload) (at 575/690V) [A]
144
171
211
266
319
Continuous KVA(at 550V) [KVA]
131
154
191
241
289
Continuous KVA(at 575V) [KVA]
130
154
191
241
289
Continuous KVA(at 690V) [KVA]
157
185
229
289
347
Max. input current
130BA229.10
Continuous (at 550V) [A]
130
158
198
245
299
Continuous (at 575V) [A]
124
151
189
234
286
Continuous (at 690V) [A]
128
155
197
240
296
Max. cable size, line power motor, load share and
brake [mm
2
(AWG)]
2 x 70 (2 x 2/0)
2 x 150 (2 x 300 mcm)
Max. external pre-fuses [A]
1
250
315
350
350
400
Estimated power loss at rated max. load [W,hp]
4)
,
600V
2533, 3.40
2963, 3.97 3430, 4.60
4051,
5.43
4867, 6.53
Estimated power loss at rated max. load [W, hp]
4)
,
690V
2662, 3.57
3430, 4.60 3612, 4.84
4292,
5.76
5156, 6.91
Weight, Enclosure IP21, IP54 (lb [kg])
211.6 [96]
229.3
[104]
275.6
[125]
299.8 [136]
Weight, Enclosure IP00 (lb [kg])
180.8 [82]
200.6 [91]
246.9
[112]
271.2 [123]
Efficiency
4)
0.98
Output frequency
0–600 Hz
Heatsink overtemp. trip
185°F [85
°
C]
194°F
[90
°
C]
230°F
[110
°
C]
230°F
[110
°
C]
230°F
[110
°
C]
Power card ambient trip
140°F [60
°
C]
Table 8.11
General Specifications and ...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
8-11
8
8