Line Power Supply 3 x 525–690V AC
P500
P560
P630
Typical Shaft output at 550V [kW]
400
450
500
Typical Shaft output at 575V [HP]
500
600
650
Typical Shaft output at 690V [kW]
500
560
630
Enclosure IP21
E1
E1
E1
Enclosure IP54
E1
E1
E1
Enclosure IP00
E2
E2
E2
Output current
130BA230.10
Continuous
(at 550V) [A]
523
596
630
Intermittent (60 sec overload)
(at 550V) [A]
575
656
693
Continuous
(at 575/690V) [A]
500
570
630
Intermittent (60 sec overload)
(at 575/690V) [A]
550
627
693
Continuous KVA
(at 550V) [KVA]
498
568
600
Continuous KVA
(at 575V) [KVA]
498
568
627
Continuous KVA
(at 690V) [KVA]
598
681
753
Max. input current
130BA229.10
Continuous
(at 550V) [A]
504
574
607
Continuous
(at 575V) [A]
482
549
607
Continuous
(at 690V) [A]
482
549
607
Max. cable size, line power, motor and load
share [mm
2
(AWG)]
4x240 (4x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500
mcm)
Max. cable size, brake [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external pre-fuses [A]
1
700
900
900
Estimated power loss
at rated max. load [W, hp]
4)
, 600 V
6903, 9.26
8343, 11.19
9244, 12.40
Estimated power loss
at rated max. load [W, hp]
4)
, 690V
7249, 9.72
8727, 11.70
9673, 12.97
Weight,
enclosure IP21, IP54 (lb [kg])
579.8 [263]
599.7 [272]
690 [313]
Weight,
enclosure IP00 (lb [kg])
487.2 [221]
520.3 [236]
610.7 [277]
Efficiency
4)
0.98
Output frequency
0–500Hz
Heatsink overtemp. trip
230°F [110
°
C]
Power card ambient trip
154.4°F [68
°
C]
Table 8.13
General Specifications and ...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
8-13