5.2.10 Control Terminals
Drawing reference numbers:
1.
10-pole plug, digital I/O.
2.
3-pole plug, RS-485 bus.
3.
6-pole, analog I/O.
4.
USB Connection.
1
4
2
3
130BA012.11
61
68
69
39
42
50
53
54
55
12
13
18
19
27
29
32
33
20
37
Figure 5.22 Control Terminals (all Enclosures)
5.2.11 Control Cable Terminals
To mount the cable to the terminal:
1.
Strip isolation of 0.34–0.39 in [9–10 mm]
2.
Insert a screw driver
1)
in the rectangular hole.
3.
Insert the cable in the adjacent circular hole.
4.
Remove the screwdriver. The cable is now
mounted to the terminal.
To remove the cable from the terminal:
1.
Insert a screw driver
1)
in the square hole.
2.
Pull out the cable.
1)
Max. 0.015 x 0.1 in [0.4 x 2.5 mm]
130BA150.10
9 - 10 mm
(0.37 in)
1.
130B
T311.10
2.
130B
T312.10
3.
Table 5.29
130B
T306.10
Figure 5.23