525–690V, frame sizes D, E and F
Size/
Type
Bussm
ann
E1250
85
JFHR2
Amps
SIBA
E18027
6
JFHR2
Ferraz-
Shawmut
E76491
JFHR2
Internal
Option
Bussmann
P45K
170M
3013
125
20610
32.125
6.6URD30D08
A0125
170M3015
P55K
170M
3014
160
20610
32.16
6.6URD30D08
A0160
170M3015
P75K
170M
3015
200
20610
32.2
6.6URD30D08
A0200
170M3015
P90K
170M
3015
200
20610
32.2
6.6URD30D08
A0200
170M3015
P110
170M
3016
250
20610
32.25
6.6URD30D08
A0250
170M3018
P132
170M
3017
315
20610
32.315
6.6URD30D08
A0315
170M3018
P160
170M
3018
350
20610
32.35
6.6URD30D08
A0350
170M3018
P200
170M
4011
350
20610
32.35
6.6URD30D08
A0350
170M5011
P250
170M
4012
400
20610
32.4
6.6URD30D08
A0400
170M5011
P315
170M
4014
500
20610
32.5
6.6URD30D08
A0500
170M5011
P400
170M
5011
550
20620
32.55
6.6URD32D08
A550
170M5011
Table 5.18 Frame Size D, E and F 525–690V
Size/
Type
Bussmann
PN*
Rating
Ferraz
Siba
P450
170M4017
700 A,
700 V
6.9URD31
D08A070
0
20 610 32.700
P500
170M4017
700 A,
700 V
6.9URD31
D08A070
0
20 610 32.700
P560
170M6013
900 A,
700 V
6.9URD33
D08A090
0
20 630 32.900
P630
170M6013
900 A,
700 V
6.9URD33
D08A090
0
20 630 32.900
Table 5.19 Frame Size E, 525–690V
Size/
Type
Bussmann
PN*
Rating
Siba
Internal
Bussmann
Option
P710
170M7081
1600A,
700V
20 695 32.1600
170M7082
P800
170M7081
1600A,
700V
20 695 32.1600
170M7082
P900
170M7081
1600A,
700V
20 695 32.1600
170M7082
P1M0
170M7081
1600A,
700V
20 695 32.1600
170M7082
P1M2
170M7082
2000A,
700V
20 695 32.2000
170M7082
P1M4
170M7083
2500A,
700V
20 695 32.2500
170M7083
Table 5.20 Frame Size F, Line Fuses, 525–690V
Size/Type
Bussmann
PN*
Rating
Siba
P710
170M8611
1100A,
1000V
20 781 32. 1000
P800
170M8611
1100A,
1000V
20 781 32. 1000
P900
170M8611
1100A,
1000V
20 781 32. 1000
P1M0
170M8611
1100A,
1000V
20 781 32. 1000
P1M2
170M8611
1100A,
1000V
20 781 32. 1000
P1M4
170M8611
1100A,
1000V
20 781 32.1000
Table 5.21 Frame size F, Inverter Module DC Link Fuses, 525–690V
*170M fuses from Bussmann shown use the -/80 visual indicator, -
TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size
and amperage may be substituted for external use.
Suitable for use on a circuit capable of delivering not more
than 100 000 rms symmetrical amperes, 500/600/690 Volts
maximum when protected by the above fuses.
Supplementary fuses
Frame size>
Bussmann PN*
Rating
D, E and F
KTK-4
4 A, 600 V
Table 5.22 SMPS Fuse
How to Install
VLT
®
HVAC Drive Design Guide
5-20
MG11BB22 - VLT
®
is a registered Danfoss trademark
5
5