5.8.3 Direction of Motor Rotation
The default setting is clockwise rotation with the frequency converter
output connected as follows.
Terminal 96 connected to U-phase
Terminal 97 connected to V-phase
Terminal 98 connected to W-phase
The direction of motor rotation is changed by switching two motor pha-
ses.
Motor rotation check can be performed using par. 1-28
Motor Rotation
Check and following the steps shown in the display.
5.8.4 Motor Thermal Protection
The electronic thermal relay in the frequency converter has received the UL-approval for single motor protection, when par. 1-90
Motor Thermal Protec-
tion is set for ETR Trip and par. 1-24 Motor Current is set to the rated motor current (see motor name plate).
5 How to Install
Automation VT Drive FC322 Design Guide
178
MG.20.X1.22 - VLT
®
is a registered Danfoss trademark