Set Preset reference 0 to first preset speed (par. 3-10
Preset Reference [0]) in percentage of Max reference speed (par. 3-03 Maximum Reference). Ex.:
60%
Set preset reference 1 to second preset speed (par. 3-10
Preset Reference [1] Ex.: 0 % (zero).
Set the timer 0 for constant running speed in par. 13-20
SL Controller Timer [0]. Ex.: 2 sec.
Set Event 1 in par. 13-51
SL Controller Event [1] to True [1]
Set Event 2 in par. 13-51
SL Controller Event [2] to On Reference [4]
Set Event 3 in par. 13-51
SL Controller Event [3] to Time Out 0 [30]
Set Event 4 in par. 13-51
SL Controller Event [1] to False [0]
Set Action 1 in par. 13-52
SL Controller Action [1] to Select preset 0 [10]
Set Action 2 in par. 13-52
SL Controller Action [2] to Start Timer 0 [29]
Set Action 3 in par. 13-52
SL Controller Action [3] to Select preset 1 [11]
Set Action 4 in par. 13-52
SL Controller Action [4] to No Action [1]
Set the Smart Logic Control in par. 13-00
SL Controller Mode to ON.
Start / stop command is applied on terminal 18. If stop signal is applied the frequency converter will ramp down and go into free mode.